Locating the Units

In new construction, it’s obviously best to plan the installation so that the mechanical unit is as far as possible from neighboring windows. A certain amount of noise reduction can be expected when sound travels from the unit to the nearest bedroom window (if we are worried about the owner of the outdoor unit), or the nearest boundary line (if we are worried about the neighbor or code compliance). But other variables need to be taken into account as well: Topography, ground cover, nearby structures, and even atmospheric conditions can bend the acoustic wave up or down, making it louder or quieter.

There are various formulas for calculating the net result of these ground and scattering effects, but for a quick estimate you can use what is called the inverse square law, which says that there is a 6 dB decrease of sound pressure level (SPL) per doubling of the distance. If the manufacturer’s SPL was recorded 3 feet away from the unit, moving 6 feet away from the unit would yield a 6 dB reduction; for an additional 6 dB reduction, you’d have to move 12 feet away.


Calculating Noise Reduction Based on Barrier Heights

Noise levels (measured in dB) vary depending on the source’s sound power level, site conditions, and the distance between the source and the receiver. In order to be considered a nuisance or noise code violation, noise levels must exceed a specified amount at a given location, typically 3 feet inside the nearest window, as shown in (A). Placing a high-STC barrier, such as a plywood-sheathed wall lined with an acoustic blanket, between an AC condenser or other source and the receiver will provide additional noise reduction, as shown in (B) and (C). To predict whether noise reduction levels from barriers of different heights will provide sufficient noise reduction levels at specific frequencies, the author uses the chart below. Because decibels are a logarithmic measurement, even a modest 10 dB decrease represents a 90 percent change in sound energy — which the ear will perceive as being half as loud as the original noise (see table at bottom).

  • Image

    A "quiet" condenser that measures 72.3 dB at 3 feet will measure about 60 dB at 12 feet, according to the inverse square rule (doubling the distance yields a reduction of about 6 dB).

  • Image
    Placing a 5-foot-tall barrier no more than 3 feet away frome the condenser will reduce noise levels at the window by 6.6 dB at 125 Hz.
  • Image
    A 10-foot-tall barrier will reduce noise levels at the window by 14.1 dB at 125 Hz.

 


Existing Installations

When an existing installation is causing a noise problem, I start by identifying the frequency and decibel level of the noise coming from the mechanical unit. We usually measure these levels with a sound meter, but you can sometimes get good acoustic data from the manufacturer. “Sound ratings” that don’t specify the weighting of the reading or the distance that the reading was taken from the unit (requirements of most noise codes) aren’t very useful. What we prefer to see are octave band levels that indicate which frequencies have the highest decibel ratings, detailed with information about weighting and distance, rather than a vague single-digit rating number. If I’m using information from the manufacturer, I keep in mind that its figures are only estimates and that on-site noise levels often are higher.

  • Image
    Octave bands indicate a mechanical unit’s noise levels at specific frequencies and are therefore more useful than single-number “average” sound ratings when designing barriers and enclosures. As this chart indicates, most AC condensers are noisier at lower frequencies.
I also refer to the manufacturers’ specifications when I’m trying to determine the correct treatment for structure-borne noise, to find out the weight of the unit and the rpm of the motor.

If there’s a local noise ordinance, it will usually specify the acceptable noise level for different sources of sound. In New York City, the noise-level limit for a single AC unit is 42 dB(A) as measured from 3 feet inside the nearest open window. But most noise ordinances also require that noise levels don’t exceed ambient — or background — noise levels by more than a certain amount when the unit is turned on. So I use a sound meter to estimate ambient levels and refer to them when setting noise-reduction goals.

For example, if the SPL of a condenser is 73 dB(A), and the acceptable noise level is 42 dB(A), the theoretical target noise-reduction level would be 31 dB. Code officials in New York currently enforce a limit of 3 to 4 dB over ambient levels, which often can measure as much as 48 dB(A) in the city. That means that the acceptable noise level for the unit may actually be as high as 52 dB(A), and the target noise-reduction level would be 21 dB.

Cost

Costs for building soundproofing enclosures can vary widely depending on site conditions and noise-reduction goals. For instance, the materials to build a two-sided enclosure for the pre-existing AC condenser shown the slideshow cost only $1,300. We didn’t have to satisfy any noise codes, just a nearby neighbor, and the enclosure height was limited to 5 feet to avoid blocking the view out of the windows.

The cost to design and build the 10-foot-tall soundproofing barrier for the standby generator in the slideshow was about $15,000, including materials and installation. This barrier had to block enough noise for the generator to comply with local noise ordinances, yet not exceed zoning height restrictions.

Bonnie Schnitta is the owner of SoundSense, an acoustic consulting firm and manufacturer of sound-control products.