A.Scott McVicker, S.E., of McVicker
Associates, Inc., Structural Engineers in Half Moon Bay,
Calif., responds: Let's look at the second condition first (see
illustration, right): The vent holes in the diaphragm blocking
are positioned at the top of the blocks, so they clear the
insulation. As far as strength goes, the 2-inch-diameter holes
will reduce the shear transfer ability of the block, but not by
so much that typical diaphragm nailing will be affected.
Here's a sample calculation, assuming that the horizontal
shear strength of the wood is 63 pounds per square inch, with a
one-third increase allowed for dynamic (seismic or wind)
loading. If the 2-by rafters are spaced 24 inches on-center,
the blocks are 22 1/2 inches long. Assume that for venting you
need three 2-inch-diameter holes spaced equally along the
block. The remaining area of wood between the holes will be
16.5 inches in length (22.5 - 6). With 2-by blocking, that
gives 24.75 square inches of shear area (16.5)(1.5). The
maximum force to be resisted by each block will be the
remaining area times the allowable stress: (24.75)(63)(1.33) =
2,073 pounds total, or 1,036 pounds per foot, which is off the
chart for typical diaphragm nailing, so no problem there.

Now let's look at the hidden vent detail featured in JLC
(photo, above). Assume that we're using sawn lumber at 19
percent moisture content, which will shrink following
construction. The outermost block in the photo will receive the
diaphragm nailing. (Its top should have been beveled to match
the slope of the roof; otherwise, the diaphragm nails will be
subject to bending where they cross the gap.) I note that these
blocks are toenailed into the rafters, which is okay so
far.
Now look at my detail ("Hidden Vent-Screen Detail,"). The
shear is transferred from the exterior block to the vertical
spacer blocks — but at the bottom only. (If the exterior
block were nailed to the vertical block along its full height,
it would fracture as it dried and shrank.) The vertical spacer
blocks, in turn, are nailed to the interior block, which is
attached to the top plate using a metal clip. There you have
it: The shear transfer path is complete.
This detail has a couple of possible limitations. First, as
the photo shows, the contractor assumes that when the rafters
and blocking shrink, they will not shrink beyond the 1/2-inch
gap provided between the top of the vertical spacer block and
the bottom of the sheathing. Time will tell: Bumps at the edge
of the roof would be a sign that more space should have been
provided.
Second, there is a practical limit on the number of nails one
can use before the individual pieces tend to split. I could see
four 10ds at each end of the exterior block and four 10ds from
the vertical block to the interior block. Assuming 90 pounds
per nail, the maximum lateral load would be: (8)(90
lb./nail)(1.33) = 957.6 lb. per 2-foot rafter spacing, or 478
lb./ft. This is certainly not in the same league as the blocks
with drilled holes, but is probably sufficient for low shear
conditions.