By Joe Loferski, Frank Woeste,
Ricky Caudill, Terry Platt, and Quintin Smith
In August 2003, we
ran the article
"Attaching
Deck Ledgers," in which authors Cheryl
Anderson, Frank Woeste, and Joe Loferski presented
fastener schedules based on code-referenced
structural design methods. Though the number
crunching was accurate, some of the bolt and lag
spacings seemed impossibly conservative, as both
the article and several follow-up letters pointed
out. Even before the article reached your mailbox,
Joe Loferski and Frank Woeste had agreed to build
samples of the ledger-to-band-joist connections and
test them in the wood science lab at Virginia Tech.
The tests would show how theoretical structural
connections designed using engineering formulas
compared with the actual connections, tested to
destruction under code loads. As promised (Letters,
11/03), here are the results. You'll find them a
little more builder friendly. Many thanks to Joe,
Frank, and team for undertaking this important
work.
Unfortunately, just as we bring greater focus to
one area of deck construction, another issue has
reared its head — the corrosive nature of the
new pressure-treating chemicals coming onto the
market. Extensive testing by connector manufacturer
Simpson-StrongTie has shown the new treatment
formulations to be more than twice as corrosive to
hardware as the CCA treatment that is being pulled
from the market. We plan to look more closely at
this issue in the future; for now, it's best to
play it safe when working with the new
pressure-treated lumbers and stick to minimum G185
galvanized hangers and hot-dipped fasteners, or
stainless-steel hangers and fasteners. Do not mix
stainless with galvanized. For more information,
see the box at the end of the
article.--Don
Jackson |
Introduction
In the article
"Attaching Deck
Ledgers" (8/03), the authors used a procedure from the
National Design Specification for Wood Construction (NDS-2001)
to calculate the required on-center spacing of lag screws and
bolts for deck-ledger-to-band-joist connections for various
deck widths. Although the calculated spacings were "to code,"
they were too tight to be practical. The reason is that the NDS
limits the allowable load for lag screws and bolt connections
based on a very small "deformation" at the design load —
a deformation limit intended to prevent undesirable movement of
a wood-framed structure and to prevent finishes such as tile
and drywall from cracking.
The purpose of this article is to report the results of load
tests conducted on four connection details that could be used
to connect a residential deck ledger board to the house band
joist. Using this test approach, which is recognized by the
code, we found that the "allowable" loads for lag screws, for
example, are two to three times higher than the values obtained
using the NDS-2001 equations. Bolts proved to be even stronger
compared with NDS-designed connections.
The deflection of the ledger relative to the band joist (see
Figure 1) was measured at full design load. The range of
deflections for the 15 samples of each detail tested is noted,
so that the deck designer can judge whether the expected
displacement is acceptable.
The testers measured the displacement of
the ledger relative to the band joist for every specimen. The
range of displacement for each connection detail is listed with
the fastener schedule.
Code Allowance for Load
Testing
The International Building Code (IBC, 2000 and 2003 editions),
as well as previous codes, allows for load testing when "a
construction is not capable of being designed by approved
engineering analysis" or "does not comply with applicable
material design standards."
In the case of deck ledger connections to the main structure,
the minimum required fastener penetration of a lag screw into
the house band joist is four times the fastener diameter (4D).
This requirement cannot be met when you use 1/2-inch-diameter
lag screws to attach the ledger to the band joist, because a
typical band joist is only 1 1/2 inches thick (3D), not the
required 2 inches thick (4D). Even if the band were 2 inches
thick, the 1/2-inch lag screw values in the NDS-2001 tables
must be reduced by half because they are based on lag screw
penetration into the main member (the band joist) of eight
diameters (8D), or 4 inches.
Similarly, there are no available tables for designing a
bolted ledger employing drainage spacers, or even for a ledger
attached on top of structural sheathing (the NDS assumes the
connected members are in direct contact).
Therefore, we tested simulated ledger-to-band connections and
calculated allowable on-center spacings based on the ultimate
capacity of the connection, applying a safety factor and an
adjustment for load duration. The test load duration was about
five minutes, whereas the assumed duration for an occupancy
live load (40 psf for deck or 60 psf for balconies) is ten
years.
Code Language on Decks
Note that the International Residential Code (IRC 2003,
R502.2.1 Decks) states: "Where supported by attachment to an
exterior wall, decks shall be positively anchored to the
primary structure and designed for both vertical and lateral
loads as applicable. Such attachment shall not be accomplished
by the use of toenails or nails subject to
withdrawal...."
This section means that nails alone cannot be used to connect
a ledger to a band joist when no other lateral bracing is in
place to positively anchor the deck to the building against
lateral loads. Thus, in the absence of adequate lateral
bracing, lag screws, bolts, or some other positive connection
will be required to design and build a code-compliant
deck.
Test Setup
For the test, we fabricated specimens from 2x10 No. 2
spruce-pine-fir (SPF) lumber to simulate the band joist of the
house. These were attached to a 2x8 No. 2 CCA-pressure-treated
southern pine (SP) ledger board sample. We used either
1/2-inch-diameter lag screws or 1/2-inch-diameter bolts for all
tests. Some specimens included 15/32-inch APA-rated plywood to
simulate the gap produced by conventional wall sheathing
between the ledger and band joist. One test case included a
1/2-inch stack of washers between the ledger board and the
plywood to replicate the drainage space sometimes incorporated
into the connection, a practice shown in some deck design books
and in past JLC articles.
The 2-by band joist was supported on the testing machine base
to simulate direct bearing on the foundation sill plate (Figure
2).
Figure 2.The hydraulic test machine put pressure
on a pair of joists attached by hangers to the sample ledger
(top). Extra fasteners in the hangers ensured that failure
would occur not at the hanger but in the lag screw or bolt
attaching the sample ledger to the sample band joist. A
transducer measured displacement of the ledger (bottom left),
while a computer continuously recorded measurement and load
data. The load was applied until the connection failed (bottom
right).
The CCA-pressure-treated sample deck components consisted of
two 2x8 joists attached to a 2x8 ledger with joist hangers. We
used extra fasteners to attach the joist hangers to the ledger
to ensure that failure would occur in the lag screw or bolt
connection. The far end of the deck joists were supported on
solid spacers on the base of the testing machine.
We realize that CCA-treated lumber is now restricted in
residential applications, but at the time of the testing, we
needed to include an unseasoned (wet) ledger as part of the
test, and CCA was locally available. After testing, we verified
that the ledger material was "green" — that is, having a
moisture content well above 19%. By using unseasoned ledgers in
our tests, we had no need to apply an adjustment to our test
results for "wet service use."
On the specimens that included sheathing, the plywood was
trimmed so it was 2 inches shorter than the width of the ledger
board to prevent it from accidentally bearing on the test
platform and artificially inflating our tested lag or bolt
connection.
A universal hydraulic testing machine applied the load, at a
constant rate of 1/2 inch of deflection per minute. The
deflection was measured by an electronic transducer attached to
the ledger board in such a way that it measured the vertical
displacement of the ledger board relative to the band joist.
During testing, the load and displacement data were
continuously recorded by a computer.
The load was applied to the specimen at the center of the
joist, and the load measured by the testing machine was divided
by two to account for the reaction at the opposite end of the
joist. In other words, half the load was applied to the
connection itself, and half the load was applied to the
foundation at the opposite end of the joists, just as in a real
deck. The load was applied until the connection failed to carry
any additional load.
Lag Screw and Bolt
Installation
We followed the rules prescribed in NDS-2001 for fastener
installation as they relate to clearance, lead-hole diameters,
and use of washers. For lag screws, two hole diameters are
specified, a slightly larger clearance hole to allow the
nonthreaded portion to penetrate the side member (ledger)
without splitting and a smaller lead hole in the main member
(band joist) to fully engage the threads.
We purchased 1/2-inch-diameter lag screws from a local
building supply store and measured the root diameter of the
threaded portion of the screws. The root diameter was 0.39
inch, so we used a 3/8-inch lead hole, which is slightly
smaller than the root diameter, to accommodate the threads of
the lag screw in the band joist. We used a 1/2-inch clearance
hole in the CCA-treated ledger board to accommodate the
nonthreaded portion of the shank. We tightened the connections
normally, by hand with a wrench. In general, when installing
lag screws, you should feel significant turning resistance;
otherwise, the lead hole may be too large. Washers were not
used under the lag screw heads because NDS does not require
them. However, we believe that a washer on a lag screw will
improve the connection, and we would use them on our own
projects for added safety.
For the bolted connections, the NDS-2001 requires the holes to
be a minimum of 1/32 inch to a maximum of 1/16 inch larger than
the bolt diameter. Therefore, we drilled 9/16-inch holes in
both the ledger board and the band joist to accommodate the
1/2-inch bolts. We added washers on both sides of the bolt
connections as specified by NDS: one between the head and the
lumber, and the other between the nut and the lumber.
Four Cases Tested
We tested four different cases to represent common
construction practices. Fifteen replications of each case were
tested. Case 1 included a 2x8 SP ledger attached to a 2x10 SPF
band joist with a 3.5-inch-long by 1/2-inch-diameter lag screw.
Note that we used a 3.5-inch screw, because the tip of a lag
screw is not effective in load transfer. Case 2 incorporated
the 2x10 SPF band joist and 2x8 SP ledger with a 15/32-inch
plywood spacer to simulate the wall sheathing commonly
sandwiched between the ledger board and the band joist. We
connected the ledger to the band with 4-inch-long by
1/2-inch-diameter lag screws. Case 3 included the 2x10 SPF band
joist, 2x8 SP ledger, and the 15/32-inch plywood layer,
connected with a 1/2-inch-diameter bolt with washers. Case 4
was similar to Case 3, except that we added a 1/2-inch stack of
washers — the drainage space — between the plywood
and ledger to simulate a nearly 1-inch gap (including the
plywood) between the ledger and the band joist.
Case 1:
1/2-Inch Lag Screw Joist span (ft.) | | | 10 | 12 | 14 | 16 | 18 | Fastener spacing
(in.) | 34 | 25 | 20 | 17 | 15 | 13 | 11 |
The tested deflection of the ledger relative
to the band joist at design load (50 psf) ranged
from 0.03 in. to 0.17 in. LimitationsLumber size
This schedule is valid only for 2x8 or larger
ledgers with a specific gravity, G, of 0.55 or
greater (G for southern pine = 0.55) and 2-by band
joists with G of 0.42 or greater (G for SPF =
0.42). Lumber type
Tabulated fastener spacings are based on virgin
lumber with no decay. Flashing must be properly
applied to keep water from penetrating the joint
and wetting the untreated band joist. The deck
ledger must be pressure treated with an approved
chemical and retention. In the case of new home
construction, a pressure-treated house band in the
deck area is recommended. Loads
The tabulated spacings apply to residential decks
(40-psf live load, 10-psf dead load) and do not
apply to residential balconies (60-psf live load)
or other applications having design loads greater
than 40-psf live load plus 10-psf dead load. Lag screw
installation
The results apply only to 1/2-inch-diameter lag
screws long enough to fully penetrate the band
joist, not counting the tapered lag screw point.
Lead holes in the band joist for lag screws must be
drilled slightly smaller than the root diameter of
the threads, so that the threads fully engage the
main member. The clearance hole in the deck ledger
must be drilled to the same diameter as the
nonthreaded shank. Lag screws should be staggered
to guard against splitting. Joist
configuration
The tabulated spacings apply to deck construction
where the joists are laid out 24 inches on-center
or less and run perpendicular to the ledger. The
spacings do not apply to deck construction where
the deck joists are parallel to the ledger and
joist loads are transferred to the ledger using
widely spaced girders. That produces a large
concentrated load on the ledger; in that case,
design by a professional is required. Inspection
Deck framing and connections should be inspected
annually to detect possible deterioration.
|
Joist span
(ft.) | | | 10 | 12 | 14 | 16 | 18 | Fastener spacing
(in.) | 30 | 23 | 18 | 15 | 13 | 11 | 10 |
The tested deflection of the ledger relative
to the band joist at design load (50 psf) ranged
from 0.08 in. to 0.24 in. LimitationsLumber size
This schedule is valid only for 2x8 or larger
ledgers with a specific gravity, G, of 0.55 or
greater (G for southern pine = 0.55) and 2-by band
joists with G of 0.42 or greater (G for SPF =
0.42). Lumber type
Tabulated fastener spacings are based on virgin
lumber with no decay. Flashing must be properly
applied to keep water from penetrating the joint
and wetting the untreated band joist. The deck
ledger must be pressure treated with an approved
chemical and retention. In the case of new home
construction, a pressure-treated house band in the
deck area is recommended. Loads
The tabulated spacings apply to residential decks
(40-psf live load, 10-psf dead load) and do not
apply to residential balconies (60-psf LL) or other
applications having design loads greater than
40-psf live load plus 10-psf dead load. Lag screw
installation
The results apply only to 1/2-inch-diameter lag
screws long enough to fully penetrate the band
joist, not counting the tapered lag screw point.
Lead holes in the band joist for lag screws must be
drilled slightly smaller than the root diameter of
the threads, so that the threads fully engage the
main member. The clearance hole in the deck ledger
must be drilled to the same diameter as the
nonthreaded shank. Lag screws should be staggeredto
guard against splitting. Sheathing
The test results apply to wall sheathing
thicknesses of 15/32 inch or less. Joist
configuration
The tabulated spacings apply to deck construction
where the joists are laid out 24 inches on-center
or less and run perpendicular to the ledger. The
spacings do not apply to deck construction where
the deck joists are parallel to the ledger and
joist loads are transferred to the ledger using
widely spaced girders. That produces a large
concentrated load on the ledger; in that case,
design by a professional is required. Inspection
Deck framing and connections should be inspected
annually to detect possible deterioration.
|
Joist span (ft.) | | | 10 | 12 | 14 | 16 | 18 | Fastener spacing
(in.) | 36* | 36* | 34 | 29 | 24 | 21 | 19 |
The tested deflection of the ledger relative
to the band joist at design load (50 psf) ranged
from 0.11 in. to 0.35 in. *These spacings have been reduced from the
allowable value determined by testing in
consideration of the ledger's bonding strength
between bolts. LimitationsLumber size
This schedule is valid only for 2x8 or larger
ledgers with a specific gravity, G, of 0.55 or
greater (G for southern pine = 0.55) and 2-by band
joists with G of 0.42 or greater (G for SPF =
0.42). Lumber type
Tabulated fastener spacings are based on virgin
lumber with no decay. Flashing must be properly
applied to keep water from penetrating the joint
and wetting the untreated band joist. The deck
ledger must be pressure treated with an approved
chemical and retention. In the case of new home
construction, a pressure-treated house band in the
deck area is recommended. Bolt installation
The results apply only to 1/2-inch-diameter bolts
of sufficient length to allow for a washer under
the head and a washer under the nut. Holes for
bolts must be drilled 1/32 to 1/16 inch larger than
the bolt diameter. Bolts should be staggered to
guard against splitting. Sheathing
The test results apply to wall sheathing
thicknesses of 15/32 inch or less. Joist
configuration
The tabulated spacings apply to deck construction
where the joists are laid out 24 inches on-center
or less and run perpendicular to the ledger. The
spacings do not apply to deck construction where
the deck joists are parallel to the ledger and
joist loads are transferred to the ledger using
widely spaced girders. That produces a large
concentrated load on the ledger; in that case,
design by a professional is required. Inspection
Deck framing and connections should be inspected
annually to detect possible deterioration.
|
Joist span (ft.) | | | 10 | 12 | 14 | 16 | 18 | Fastener spacing
(in.) | 36* | 36* | 30 | 25 | 21 | 19 | 17 |
The tested deflection of the ledger relative
to the band joist at design load (50 psf) ranged
from 0.25 in. to 0.42 in. *These spacings have been reduced from the
allowable value determined by testing in
consideration of the ledger's bonding strength
between bolts. LimitationsLumber size
This schedule is valid only for 2x8 or larger
ledgers with a specific gravity, G, of 0.55 or
greater (G for southern pine = 0.55) and 2-by band
joists with G of 0.42 or greater (G for SPF =
0.42). Lumber type
Tabulated fastener spacings are based on virgin
lumber with no decay. Flashing must be properly
applied to keep water from penetrating the joint
and wetting the untreated band joist. The deck
ledger must be pressure treated with an approved
chemical and retention. In the case of new home
construction, a pressure-treated house band in the
deck area is recommended. Loads
The tabulated spacings apply to residential decks
(40-psf live load, 10-psf dead load) and do not
apply to residential balconies (60-psf LL) or other
applications having design loads greater than
40-psf live load plus 10-psf dead load. Bolt Installation
The results apply only to 1/2-inch- diameter bolts
of sufficient length to allow for a washer under
the head and a washer under the nut. Holes for
bolts must be drilled 1/32 to 1/16 inch larger than
the bolt diameter. Bolts should be staggered to
guard against splitting. Sheathing
The test results apply to wall sheathing
thicknesses of 15/32 inch or less. Spacers
Where spacers are used for drainage, the gap
between the ledger and the wall sheathing created
by the spacers must be 1/2 inch or less. Joist
configuration
The tabulated spacings apply to deck construction
where the joists are laid out 24 inches on-center
or less and run perpendicular to the ledger. The
spacings do not apply to deck construction where
the deck joists are parallel to the ledger and
joist loads are transferred to the ledger using
widely spaced girders. That produces a large
concentrated load on the ledger; in that case,
design by a professional is required. Inspection
Deck framing and connections should be inspected
annually to detect possible deterioration.
|
Safety factor applied. To
determine allowable fastener spacings, we calculated the
maximum average load for each case and reduced the results by
factors to account for safety and the fact that the laboratory
tests were of short duration.
The IBC requires that failure loads from tests of structural
assemblies be divided by a safety factor of 2.5. For the
purpose of decks, we used an even larger safety factor, of 3.0,
to further account for possible variations in field
installation of lag screws and bolts.
The average maximum load was further reduced by a load duration
factor of 1.6 to account for the difference in performance
between short-term laboratory testing (about five minutes) and
ten-year continuous loading as defined for occupancy live load
in the NDS.
Wet-use factor not needed.
The NDS requires a "wet-use" reduction factor (Cm )
to be applied to connection design values for situations where
the wood is expected to be above 19% moisture content. For
those tests, we used wet CCA-treated southern pine ledger
boards, with an average moisture content of 44%. Because we
expect the moisture content of deck lumber to remain above 19%
during periods of wet weather, we applied no reduction in the
calculated design strength; the effect of using wet lumber is
included in the test.
Deck loads. After applying
these reduction factors, the resulting values were used to
calculate the required spacing between fasteners for various
joist spans based on a design loading of 40-psf live load and
10-psf dead load, as specified in the IRC for residential
decks. However, because residential balconies have a higher
design load than residential decks, these spacing results do
not apply to balconies.
Failures of Lag Screws vs.
Bolts
The fastener spacings for the bolted connections (Cases 3 and
4) are considerably larger than for those of the lag screws
(Cases 1 and 2). At high test loads, the washers under the head
and nut keep the bolt from withdrawing completely from the
connection; thus the ultimate loads for the bolted specimens
were generally greater. For lag screw specimens, failure often
occurred when the threaded shank withdrew from the band joist
or when the head of the lag screw embedded itself into the
ledger. Also, due to the threads, lag screws have a reduced
diameter in the band joist, and thus the screw rotates more
easily under load than a bolt of the same nominal size.
Expected deformations. The
tables include the measured range of vertical deformation
between the band and the ledger for each case. These numbers
provide an estimate of the expected range of deformation at
full design load for a short period of time. If the live load
on a deck is sustained — for instance, from heavy
planters — this expected deflection of the ledger
relative to the band joist may be double the stated figure, or
even greater. Judgment is needed in using this data for
particular cases of significant sustained live loads. Occupant
loading on a deck is not considered sustained.
Limitations of Results
The strength of mechanical connectors used in wood construction
depends partly on the specific gravity, G, of the lumber.
Southern pine, the ledger material we used, has a G of 0.55;
SPF, the sample band joist, has a G of 0.42.
The main disadvantage of this test-based approach is that the
allowable values cannot be extrapolated downward for materials
having a lower strength. For example, we cannot use the test
data to predict the strength of a lag screw connection made
with a pressure-treated hem-fir ledger (G = 0.43). It would be
acceptable to use the schedules with a hem-fir band joist,
however, as long as the ledger was southern pine.
Joe Loferski and Frank Woeste,
P.E.,are professor and professor
emeritus, respectively, in the Department of Wood Science and
Forest Products at Virginia Tech University, Blacksburg.Ricky Caudillis a lab technician,Terry Platta research scientist, andQuintin Smitha summer intern in the department. At the
end of April, Drs. Woeste and Loferski will conduct a short
course entitled Liability Issues, Design Data, and Inspection
Techniques for Wood Decks, Balconies, and Porches. To learn
more, visit www.conted.vt.edu/sdww.